Regulations
/
EnEfG
/
Edit measure
Edit measure
Title (English)
Title (German)
Obligations
Implement an energy or environmental management system
Draw up and publish implementation plans for economically viable final energy savings measures
Have the implementation plans confirmed before publication
Submit evidence on the management system within four weeks when ordered to do so
Operate an existing data centre with a power usage effectiveness of 1.5 or below from 1 July 2027
Operate an existing data centre with a power usage effectiveness of 1.3 or below from 1 July 2030
Build and operate a new data centre with a power usage effectiveness of 1.2 or below
Achieve the required share of reused energy in the data centre
Cover half of the data centre's electricity consumption with electricity from renewable sources on a balance-sheet basis
Cover the data centre's electricity consumption entirely with electricity from renewable sources on a balance-sheet basis
Implement and operate an energy or environmental management system for the data centre
Have the energy or environmental management system validated or certified
Publish the data centre information annually and transmit it to the Federation
Present the customer-specific energy consumption to customers
Avoid waste heat in line with the state of the art and reduce it to the unavoidable share
Reuse the waste heat arising
Provide information on the waste heat arising on request
Transmit the waste heat information annually to the Federal Office for Energy Efficiency
Have the energy or environmental management system validated or certified
Description (English)
The electrical power and energy demand of the main components are measured continuously; from this the power usage effectiveness under DIN EN 50600-4-2 is determined as an annual average. The measured values are also the basis for the information under Annex 3.
Description (German)
Die elektrische Leistung und der Energiebedarf der wesentlichen Komponenten werden kontinuierlich gemessen; daraus wird die Energieverbrauchseffektivität nach DIN EN 50600-4-2 als Jahresdurchschnitt ermittelt. Die Messwerte sind zugleich Grundlage der Angaben nach der Anlage 3.