Emtract Ingest
API
EN
EN
DE
Dashboard
Regulations
Crawlers
Attributes
Topics
Home
/
Regulations
/
EnEfG
/
Edit obligation
Edit obligation
Title (English)
Title (German)
Kind
Approval
Due Diligence
Governance
Other
Record Keeping
Reporting
Stakeholder Engagement
Frequency
Annual
Biennial
Continuous
Event-triggered
Monthly
One-time
Other
Quarterly
Weekly
Check frequency
Annual
Biennial
Continuous
Event-triggered
Monthly
One-time
Other
Quarterly
Weekly
Rule set
Regulation-wide (no rule set)
Companies with an average annual total final energy consumption of more than 7.5 gigawatt hours
Companies with an average annual total final energy consumption of more than 2.5 gigawatt hours
Operators of data centres
Data centres that started operation before 1 July 2026
Data centres that start operation from 1 July 2026
Data centres with a non-redundant rated connected load of 1 megawatt and above
Operators of data centres offering services to third parties
Data centres owned by or operated for public bodies
Complexity (0–5)
Business functions
Communications
Compliance
Executive
Finance
Human Resources
Legal
Operations
Other
Procurement
Product
Sales
Sustainability
Description (English)
A data centre that started or starts operation before 1 July 2026 must be built and operated so as to achieve a power usage effectiveness of 1.5 or below from 1 July 2027. Power usage effectiveness is defined in Section 3 as the ratio of the annual energy demand of the entire data centre to the energy demand of the information technology, within the meaning of DIN EN 50600-4-2. This is the first of two steps; from 1 July 2030 the stricter value of 1.3 applies and is recorded as a separate obligation.
Description (German)
Ein Rechenzentrum, das vor dem 1. Juli 2026 den Betrieb aufgenommen hat oder aufnimmt, ist so zu errichten und zu betreiben, dass es ab dem 1. Juli 2027 eine Energieverbrauchseffektivität von kleiner oder gleich 1,5 erreicht. Die Energieverbrauchseffektivität ist nach § 3 das Verhältnis des jährlichen Energiebedarfs des gesamten Rechenzentrums zum Energiebedarf der Informationstechnik im Sinne der DIN EN 50600-4-2. Dies ist die erste von zwei Stufen; ab dem 1. Juli 2030 gilt der strengere Wert von 1,3, der als eigene Pflicht geführt wird.
Affected products/services (English)
The data centre, including the information technology operated in it and the building services installations.
Affected products/services (German)
Das Rechenzentrum einschließlich der darin betriebenen Informationstechnik und der betriebstechnischen Anlagen.
Checking responsibility (English)
Data centre operations management.
Checking responsibility (German)
Leitung des Rechenzentrumsbetriebs.
Check method (English)
Annual average of the measured power usage effectiveness under DIN EN 50600-4-2.
Check method (German)
Jahresdurchschnitt der gemessenen Energieverbrauchseffektivität nach DIN EN 50600-4-2.